Drive, 2 standard connection diagram – Yaskawa Z1000U User Manual

Page 57

Advertising
background image

+

-

+

+

-

+

+

S

1

S

2

S

3

S

4

S

5

S

6

S

7

A

1

A

2

A

3

0 V

AC

R
R
S
S-

IG

Drive

2 k

S

8

SC

0 V

FM

AM
AC

E (G)

<11>

<8>

<10>

<7>

<4>

<3>

+

24 V

+

V

MD

M

1

M

2

ME
MF

Forward Run / Stop

Reverse Run / Stop

External fault

Fault reset

Multi-speed step 1

Multi-speed step 2

External Baseblock

Jog speed

Multi-function

digtial inputs

(default setting)

Sink / Source mode

selection wire link

(default: Sink)

CN5-C

CN5-B

CN5-A

Option board

Shield ground terminal

Multi-function

analog inputs

Power supply +10.5 Vdc, max. 20 mA

Analog Input 1 (Frequency Reference Bias)

0 to 10Vdc (20 kΩ) / 4 to 20 mA (250 Ω) / 0 to 20 mA (250 Ω)

APOGEE FLN Comm.
RS-422/RS-485
48 kbps
BACnet Comm.
RS-485
max. 76.8 kbps
MEMOBUS/Modbus
comm. RS-422/RS-485
max. 115.2 kbps
Metasys N2 Comm.
RS-422/RS-485
96 kbps

Termination resistor

(120 , 1/2 W)

DIP

Switch S2

Multi-function relay output (Speed Agree H2-03)

250 Vac, max. 1 A

30 Vdc, max 1 A

(min. 5 Vdc, 10 mA)

Multi-function relay output (During Run H2-01)

250 Vac, max. 1 A

30 Vdc, max 1 A

(min. 5 Vdc, 10 mA)

Multi-function analog output 1
(Output frequency)

-10 to +10 Vdc (2 mA)
or 4 to 20 mA

Control Circuit

shielded line

twisted-pair shielded line

main circuit terminal

control circuit terminal

M

3

M

4

Multi-function relay output (Zero Speed H2-02)

250 Vac, max. 1 A

30 Vdc, max 1 A

(min. 5 Vdc, 10 mA)

SP

SN

<9>

AM

FM

V

I

Off

On

DIP Switch S2

Term. Res. On/Off

Jumper S1
A1/A2/A3 Volt./Curr.
Selection

Jumper S5

AM/FM Volt./Curr.

Selection

Terminal board

jumpers and switches

FM

+

AM

<5>

<12>

<11>

Multi-function analog output 2
(Output current)

-10 to +10 Vdc (2 mA)
or 4 to 20 mA

connectors

Analog Input 2 (Frequency Reference Bias)

-10 to 10Vdc (20 kΩ) / 4 to 20 mA (250 Ω) / 0 to 20 mA (250 Ω)

Analog Input 3 (Aux. Frequency Reference)

0 to 10Vdc (20 kΩ) / 4 to 20 mA (250 Ω) / 0 to 20 mA (250 Ω)

Fault output

250 Vac, max. 1 A

30 Vdc, max 1 A

(min. 5 Vdc, 10 mA)

MA
MB
MC

Note: When A1 & A3 using current input

Resolution = 10 bit plus sign

V

I

A1 A2 A3

M

U/T

1

V/T

2

W/T

U
V

W

3

Ground

Main Circuit

R/L1
S/L2
T/L3

Fuse

p1

n1

Terminals p1, n1 are for connection
options. Never connect power supply
lines to these terminals.

<1>

<2>

Cooling fan

M

FU
FV

FW

ELCB (MCCB)

R

T

S

Three-phase
power supply
240 to 500 V
50/60 Hz
(Depending on
model capacity)

2MCCB

r1

s1

t1

MC

Wiring sequence should shut off
power to the drive when a fault
output is triggered.

ON
OFF

EMC filter

Switch

<13>

24

0

FE

24 V

0 V

24 V Power Supply
Terminals

<14>

<6>

Figure 3.1 Drive Standard Connection Diagram (example: model 2o0028)

3.2 Standard Connection Diagram

YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual

57

3

Electrical Installation