Terminal am/fm signal selection, Memobus/modbus termination, Table 3.14 – Yaskawa Z1000U User Manual

Page 89: 10 control i/o connections

Advertising
background image

Table 3.14 Voltage/Current Selection Parameter Details

No.

Parameter Name

Description

Setting

Range

Default

Setting

H3-01

Terminal A1 signal level selection

Selects the signal level for terminal A1.

0: 0 to 10 Vdc

1: 0 to 10 Vdc Bipolar

2: 4 to 20 mA

3: 0 to 20 mA

0 to 3

0

H3-05

Terminal A3 signal level selection

Selects the signal level for terminal A3.

0: 0 to 10 Vdc

1: 0 to 10 Vdc Bipolar

2: 4 to 20 mA

3: 0 to 20 mA

0 to 3

0

H3-09

Terminal A2 signal level selection

Selects the signal level for terminal A2.

0: 0 to 10 Vdc

1: 0 to 10 Vdc Bipolar

2: 4 to 20 mA

3: 0 to 20 mA

0 to 3

2

u

Terminal AM/FM Signal Selection

The signal type for terminals AM and FM can be set to either voltage or current output using jumper S5 on the terminal board

as explained in

Table 3.15

. When changing the setting of jumper S5, parameters H4-07 and H4-08 must be set accordingly.

The default selection is voltage output for both terminals.

Table 3.15 Jumper S5 Settings

Terminal

Voltage Output

Current Output

Terminal AM

AM

FM

V

I

AM

FM

V

I

Terminal FM

AM

FM

V

I

AM

FM

V

I

Table 3.16 Parameter H4-07 and H4-08 Details

No.

Parameter Name

Description

Setting

Range

Default

Setting

H4-07

Terminal AM signal level selection

0: 0 to 10 Vdc

1: -10 to 10 Vdc

2: 4 to 20 mA

0 to 2

0

H4-08

Terminal FM signal level selection

u

MEMOBUS/Modbus Termination

This drive is equipped with a built-in termination resistor for the RS-422/RS-485 communication connector. DIP switch S2

enables or disabled the termination resistor as shown in

Table 3.17

. The OFF position is the default. The termination resistor

should be placed to the ON position when the drive is the last in a series of slave drives.

Refer to Switches and Jumpers on

the Terminal Board on page 87

to locate switch S2.

Table 3.17 MEMOBUS/Modbus Termination Switch S2 Settings

S2 Position

Description

ON

Internal termination resistor ON

OFF

Internal termination resistor OFF (default setting)

3.10 Control I/O Connections

YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual

89

3

Electrical Installation