Yaskawa Z1000U User Manual

Page 212

Advertising
background image

One of the following settings was entered while

H1-oo = 2 (External Reference 1/2):
• b1-15 or b1-16 set to 3 but no option card is

connected

• Although b1-15 = 1 (Analog Input) and H3-02

or H3-10 are set to 0 (Frequency Bias)

Correct the settings for the multi-function input terminal parameters.

H2-oo is set to 38 (Drive Enabled) and H1-oo

is not set to 6A (Drive Enable)

HOA Keypad Display

Error Name

oPE05

Run Command/Frequency Reference Source Selection Error

Cause

Possible Solutions

Frequency reference is assigned to an option card

(b1-01 = 3) and an input option card is not

connected to the drive

Reconnect the input option card to the drive.

The Run command is assigned to an option card

(b1-02 = 3) and an input option card is not

connected to the drive

HOA Keypad Display

Error Name

oPE07

Multi-Function Analog Input Selection Error
A contradictory setting is assigned to multi-function analog inputs H3-02 or H3-10 and PI functions

conflict.

Cause

Possible Solutions

At least two analog input terminals are set to the

same function (i.e., at least two of these parameters

have the same setting: H3-02 or H3-10)

Change the settings to H3-02 and H3-10 so that functions no longer conflict.

Note:

Both 0 (Frequency Reference Bias) and F (Not Used) can be set to H3-02 and H3-10

simultaneously.

The following simultaneous contradictory

settings:

H3-02 or H3-10 = C (PI Target Value) while

b5-18 = 1 (enables b5-19 as the target PI value)

Disable one of the PI selections.

HOA Keypad Display

Error Name

oPE08

Parameter Selection Error
A function has been set that cannot be used in the motor control method selected.

Cause

Possible Solutions

In OLV/PM, parameters E5-02 to E5-07 are set to

0

When using a special-purpose motor, set E5-oo in accordance with the test report provided.

The following settings have occurred in OLV/PM:
• E5-03 does not equal 0
• E5-09 and E5-24 are both equal to 0, or neither

equals 0

• Set E5-09 or E5-24 to the correct value, and set the other to 0.
• Set the motor rated current for PM to 0 (E5-03).

Note:

Use U1-18 to find parameters that are set outside the specified setting range. When multiple errors occur simultaneously, other errors are

given precedence over oPE08.

HOA Keypad Display

Error Name

oPE09

PI Control Selection Fault
PI control function selection is incorrect. Requires that PI control is enabled (b5-01 = 1 or 3).

Cause

Possible Solutions

The following simultaneous contradictory settings

have occurred:
• b5-15 is not set to 0.0 (PI Sleep Function

Operation Level)

• The stopping method is set to either DC

Injection Braking or coast to stop with a timer

(b1-03 = 2 or 3)

• Set b5-15 to a value other than 0.0.
• Set the stopping method to coast to stop or ramp to stop (b1-03 = 0 or 1).

b5-01 is set to 1, enabling PI control, but the lower

limit for the frequency reference (d2-02) is not set

to 0 while reverse output is enabled (b5-11 = 1)

Correct the parameter settings.

b5-01 is set to 3, enabling PI control, but the lower

limit for the frequency reference (d2-01) is not 0 Correct the parameter settings.