Main Circuit Wire Gauges and Tightening Torque

Use the tables in this section to select the appropriate wires and crimp terminals.
Gauges listed in the tables are for use in the United States.

Note:

Wire gauge recommendations based on drive continuous current ratings using 75 °C 600 Vac vinyl-sheathed wire assuming ambient

temperature within 40 °C and wiring distance less than 100 m.

Consider the amount of voltage drop when selecting wire gauges. Increase the wire gauge when the voltage drop is greater

than 2% of motor rated voltage. Ensure the wire gauge is suitable for the terminal block. Use the following formula to calculate

the amount of voltage drop:

Line drop voltage (V) = 3 × wire resistance (Ω/km) × wire length (m) × current (A) × 10

-3

Refer to UL Standards Compliance on page 347

for information on UL compliance.

The wire gauges listed in the following tables are Yaskawa recommendations. Refer to local codes for proper wire gauge

selections.

n

Three-Phase 200 V Class

Table 3.3 Wire Gauge and Torque Specifications (Three-Phase 200 V Class)

Drive

Model

Terminal

For USA and Canada

For South America

Screw

Size

Tightening

Torque

N·m (lb.in.)

Recomm. Gauge

mm

2

(AWG, kcmil)

Wire Range

mm

2

(AWG, kcmil)

Recomm. Gauge

mm

2

(AWG, kcmil)

Wire Range

mm

2

(AWG, kcmil)

2o0028

R/L1, S/L2, T/L3

10

(8)

6 to 10

(10 to 8)

4

(12)

2.5 to 10

(14 to 8)

M5

2.3 to 2.7

(20.4 to 23.9)

U/T1, V/T2, W/T3

10

(8)

6 to 10

(10 to 8)

4

(12)

2.5 to 10

(14 to 8)

M5

10

(8)

6 to 16

(10 to 6)

6

(10)

6 to 16

(10 to 5)

M6

3.9 to 4.9

(34.7 to 43.4)

p1, n1

2.5

(14)

2.5 to 4

(14 to 12)

2.5

(14)

2.5 to 4

(14 to 12)

M4

1 to 1.4

(8.9 to 12.4)

2o0042

R/L1, S/L2, T/L3

16

(6)

10 to 25

(8 to 3)

10

(8)

6 to 25

(10 to 3)

M6

4 to 6

(35.4 to 53.1)

U/T1, V/T2, W/T3

16

(6)

10 to 25

(8 to 3)

10

(8)

6 to 25

(10 to 3)

M6

10

(8)

6 to 25

(10 to 3)

10

(8)

6 to 25

(10 to 3)

M8

8.8 to 10.8

(78.1 to 95.5)

p1, n1

2.5

(14)

2.5 to 4

(14 to 12)

2.5

(14)

2.5 to 4

(14 to 12)

M4

1 to 1.4

(8.9 to 12.4)

2o0054

R/L1, S/L2, T/L3

25

(4)

16 to 25

(6 to 3)

16

(5)

10 to 25

(8 to 3)

M6

4 to 6

(35.4 to 53.1)

U/T1, V/T2, W/T3

25

(4)

16 to 25

(6 to 3)

16

(5)

10 to 25

(8 to 3)

M6

16

(6)

10 to 25

(8 to 3)

10

(8)

10 to 25

(8 to 3)

M8

8.8 to 10.8

(78.1 to 95.5)

p1, n1

2.5

(14)

2.5 to 4

(14 to 12)

2.5

(14)

2.5 to 4

(14 to 12)

M4

1 to 1.4

(8.9 to 12.4)

2o0068

R/L1, S/L2, T/L3

25

(4)

25

(4 to 3)

16

(5)

16 to 25

(5 to 3)

M6

4 to 6

(35.4 to 53.1)

U/T1, V/T2, W/T3

25

(4)

25

(4 to 3)

16

(5)

16 to 25

(5 to 3)

M6

16

(6)

16 to 25

(6 to 3)

16

(5)

16 to 25

(5 to 3)

M8

8.8 to 10.8

(78.1 to 95.5)

p1, n1

2.5

(14)

2.5 to 4

(14 to 12)

2.5

(14)

2.5 to 4

(14 to 12)

M4

1 to 1.4

(8.9 to 12.4)

3.8 Main Circuit Wiring

72

YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual