1) wire types – Yaskawa Sigma-5 User Manual: Setup for Linear Motors User Manual

Page 106

Advertising
background image

3 Wiring and Connection

3.3.2 When Using a Standard Power Supply Input (Single-phase 100 V, Three-phase 200 V, or
Three-phase 400 V)

3-22

3.3.2 When Using a Standard Power Supply Input (Single-phase 100

V, Three-phase 200 V, or Three-phase 400 V)

(1) Wire Types

Use the following type of wire for main circuit.

The following table shows the wire sizes and allowable currents for three wires. Use

wires with specifications equal to or less than those shown in the table.

• 600 V grade heat-resistant polyvinyl chloride insulated wire (HIV)

Note: The values in the table are for reference only.

Cable Type

Allowable Conductor

Temperature (

°C)

Symbol

Name

IV

600 V polyvinyl chloride insulated wire

60

HIV

600 V grade heat-resistant polyvinyl chloride

insulated wire

75

AWG

Size

Nominal

Cross

Section

Diameter

(mm

2

)

Configuration

(Number of

Wires/mm

2

)

Conductive

Resistance

(

Ω/km)

Allowable Current at

Surrounding Air Temperature

(A)

30

°C

40

°C

50

°C

20

0.5

19/0.18

39.5

6.6

5.6

4.5

19

0.75

30/0.18

26.0

8.8

7.0

5.5

18

0.9

37/0.18

24.4

9.0

7.7

6.0

16

1.25

50/0.18

15.6

12.0

11.0

8.5

14

2.0

7/0.6

9.53

23

20

16

12

3.5

7/0.8

5.41

33

29

24

10

5.5

7/1.0

3.47

43

38

31

8

8.0

7/1.2

2.41

55

49

40

6

14.0

7/1.6

1.35

79

70

57

4

22.0

7/2.0

0.85

91

81

66

Advertising