3 Wiring and Connection

3.3.5 When Using More Than One SERVOPACK

3-34

3.3.5 When Using More Than One SERVOPACK

This section shows an example of the wiring when more than one SERVOPACK is
used and the precautions.

Wiring Example (Analog pulse model)

The following example shows the

Σ-V series SGDV SERVOPACK (Analog pulse

model).

Connect the alarm output (ALM) terminals for the three SERVOPACKs in series to
enable alarm detection relay 1RY to operate.

When the alarm occurs, the ALM output signal transistor is turned OFF.

Note: For M-II model, M-III model, and command option attachable type SERVOPACKs, the

pin number of ALM+ terminal is CN1-3, and that of ALM

− terminal is CN1-4.

R S T

1QF

2KM

1Ry

+24 V

L1

L2

L3

L1C

0 V

L2C

Power supply

1FLT

SERVOPACK

Linear
servomotor

Linear
servomotor

Linear
servomotor

M

L1

L2

L3

SERVOPACK

L1

L2

L3

L1C

1D

L2C

SERVOPACK

M

M

Relay
terminals

Relay
terminals

Relay
terminals

Relay
terminals

L1C

L2C

3SA

1QF
1FLT
1KM
2KM

: Molded-case circuit breaker
: Noise filter
: Magnetic contactor (for control power supply)
: Magnetic contactor (for main circuit power supply)

1Ry
1PL
1SA
2SA
3SA
1D

: Relay
: Indicator lamp
: Surge absorber
: Surge absorber
: Surge absorber
: Flywheel diode

1KM

(For servo
alarm display)

1PL

1KM

2KM

1SA

Servo power

supply ON

Servo power

supply OFF

2SA

31

32

CN1

1KM

1Ry

1KM

ALM+

ALM−

31

32

CN1

ALM−

31

32

CN1

ALM−

1Ry

ALM+

ALM+