Parameter Data Structure
SPC3 evaluates the first seven data bytes (without user prm data), or the first

eight data bytes (with user prm data). The first seven bytes are specified

according to the standard. The eighth byte is used for SPC3-specific

communications. The additional bytes are available to the application.

Byte

Bit Position

Designation

7

6

5

4

3

2

1

0

0

Lock
Reg

Unio
Req

Sync
Req

Free
Req

WD on

Res

Res

Res

Station status

1

WD_Fact_1

2

WD_Fact_2

3

MinTSDR

4

Ident_Number_High

5

Ident_Number_Low

6

Group_Ident

7

Spec_User_Prm_Byte

8 to 243

User_Prm_Data

Byte 7

Spec_User_Prm_Byte

Bit

Name

Significance

Default State

0

Dis_Startbit

The start bit monitoring in the receiver
is switched off with this bit

Dis_Startbit = 1,
Start bit monitoring is switched off.

1

Dis_Stopbit

Stop bit monitoring in the receiver is
switched off with this bit

Dis_Stopbit = 0
Stop bit monitoring is not switched off.

2

WD_Base

This bit specifies the time base used to
clock the watchdog.
WD_Base = 0: time base 10 ms
WD_Base = 1: time base 1 ms

WD_Base = 0
The time base is 10 ms.

3 to 4

Res

To be parameterized with 0

0

5

Publisher_Enable

DXB-publisher-functionality of the
SPC3 is activated with this bit

Publisher_Enable = 0, DXB-request-
telegrams are ignored;
Publisher_Enable = 1, DXB-request-
telegrams are processed

6 to 7

Res

To be parameterized with 0

0