MVI56-PDPMV1 ♦ ControlLogix Platform

Configuring the MVI56-PDPMV1 Module

PROFIBUS DPV1 Master

User Manual

ProSoft Technology, Inc.

Page 113 of 255

March 22, 2011

To use the CIPconnect Path Editor, follow these steps.
1 Configure the path between the 1756-ENBT connected to your PC and the

MVI56-PDPMV1 module. If the module is located in a remote rack, add more

racks to configure the full path. The path can only contain ControlNet or

EtherNet/IP networks. The maximum number of supported racks is six.

2 Click C

ONSTRUCT

CIP

P

ATH

to build the path in text format

3 Click OK to confirm the configured path.
The following examples should provide a better understanding on how to set up

the path for your network.

2.4.1 Example 1: Local Rack Application

For this example, the MVI56-PDPMV1 module is located in the same rack as the

1756-ENBT that is connected to the PC.

Rack 1

Slot

Module

Network Address

0

ControlLogix Processor

-

1

Any

-

2

MVI56-PDPMV1

-

3

1756-ENBT

IP=105.102.0.12


1 In the Download window, click CIP

P

ATH

E

DIT

.