MVI56-PDPMV1 ♦ ControlLogix Platform

Diagnostics and Troubleshooting

PROFIBUS DPV1 Master

User Manual

ProSoft Technology, Inc.

Page 179 of 255

March 22, 2011

4.2

LED Status Indicators: Front of MVI56 Module

The LEDs indicate the module’s operating status. The module has two sets of

LED status indicators:



MVI56 Module Status LEDs on the front of

the module near the top



PROFIBUS Master Status LEDs behind the

door on the front of the module.

4.2.1 Module Faceplate Status Indicators

Indicator

Color

Status

Indication

CFG

Green

ON

Configuration/Debug Port is active

OFF

Configuration/Debug Port is inactive

P1

Not Used

P2

Not Used

APP

STATUS

Amber

ON

Configuration Error: This LED is illuminated when the

PROFIBUS and module CRC values do not match
between input/output blocks.
Verify that the values match the values generated with

the Calculate Checksums button in ProSoft
Configuration Builder
. If they do not match, you must
manually change the values at the appropriate address

locations listed in the Input and Output block definitions

in this manual.

OFF

Normal operation.

BP ACT

Amber

ON

The LED is ON when the module is able to
communicate over the backplane.

OFF

The LED is OFF when the module is unable to

communicate with the processor. The processor is

either absent or not running.

BATT

Red

OFF

The battery voltage is OK and running.

ON

The battery voltage is low or the battery is not present.
The battery LED will illuminate briefly upon the first

installation of the module or if the unit has not had

power for an extended period of time. This behavior is

normal; however, should the LED come ON in a
working installation, please contact ProSoft

Technology.

OK

Red/
Green

OF

The card is not receiving any power and is not securely

plugged into the rack.

GREEN

The module is operating normally.

RED

The program has detected an error or is being
configured. If the LED remains RED for over 10

seconds, the processor program may be incompatible

with the module. Check the module version (page 18)

and mode (page 20) (Legacy or Flex) to determine the
correct sample ladder logic. Remove the card from the

rack and re-insert the card to restart the module’s

program.