MVI56-PDPMV1 ♦ ControlLogix Platform

Reference

PROFIBUS DPV1 Master

User Manual

ProSoft Technology, Inc.

Page 231 of 255

March 22, 2011

Normal Backplane Operation
The MVI56-PDPMV1 module’s application code initiates the data transfers at the

end of every ControlLogix PLC ladder scan. As such, the MVI56-PDPMV1

module is able to actively read and write the PROFIBUS Cyclic Input/Output data

blocks in the appropriate locations.

Input Data Block (Block ID = 1 to 4)
This block contains the previous input data received from the slaves.

Input Data Block Format (Input Image) (Local:1:I.Data Controller Tag)
You can find the contents of the Input Data Block (Input Image) in the
Local:1:I.Data user controller tags in RSLogix.

Word Offset

Start

End

Name

Description

0

199

PROFIBUS Input Data

Data received from the PROFIBUS slave devices on the
network.
Total size of the PROFIBUS Input Data block is a function of the
PROFIBUS network configuration.
Block ID 1 = Slave bytes 0 to 399
Block ID 2 = Slave bytes 400 to 799
Block ID 3 = Slave bytes 800 to 1199
Block ID 4 = Slave bytes 1200 to 1535

200

200

Last out mailbox
message ID processed
from output image

The module confirms the receipt of a mailbox by copying its ID
code (Message ID) to this register.

201

201

Current in mailbox
control index

Incremented after the module has transferred a new mailbox
response to the processor.

202

202

Current alarm control
index

Incremented after the module has transferred a new alarm to
the processor.

203

203

Reserved for future use

204

205

PROFIBUS CRC32
value

CRC32 checksum for PROFIBUS Master configuration
downloaded from configuration utility

206

207

Module CRC32 value

MVI56-PDPMV1 module configuration checksum for module
configuration downloaded from configuration utility

208

247

Reserved for future use

248

248

Write Block ID

Write block ID of Output image to receive (1 to 4 for data, 0 or -1
if no data)

249

249

Read Block ID

Read Block ID number -1 to 4

Input Block Status Data Details (Block ID = 0 to -1)
The MVI56-PDPMV1 module periodically transfers a status block to the

ControlLogix containing relevant information about the module operation (Block

IDs 0 to -1).
The types of data returned in the PROFIBUS Input Status area include: