ProSoft Technology MVI56-PDPMV1 User Manual

Page 234

Advertising
background image

Reference

MVI56-PDPMV1 ♦ ControlLogix Platform

User Manual

PROFIBUS DPV1 Master

Page 234 of 255

ProSoft Technology, Inc.

March 22, 2011

Byte Offset

Start

End

Name

Description

84

85

PROFIBUS Master
Module Status

Represents the PROFIBUS Master module’s operating status
Bit 2=Application Status
0 - Application Stopped
1 - Application Running
Bit 8=Data exchange (FBRS)
0 - There is no data exchange with any of the assigned slaves
1 - There is Data Exchange with at least one of the assigned
slaves
Bit 9=Slave input frozen/cleared (FBFC)
0 - A slave's inputs in the IN area are cleared if a slave is not in
Data Exchange
1 - A slave’s inputs in the IN area are frozen if a slave is not in
Data Exchange
Bit 12=Reset (RDR)
0 - No action
1 - A reset is requested by the PROFIBUS Master module
because a new database has been downloaded

86

89

PROFIBUS
configuration Checksum

CRC32 checksum for PROFIBUS Master configuration
downloaded from configuration utility

90

93

MVI56 Module
configuration checksum

MVI56-PDPMV1 for module configuration downloaded from
configuration utility

94

95

Application program
scan counter

MVI56-PDPMV1 module program scan counter. Can be used to
gauge application code scan time performance

96

97

Module PROFIBUS
output image data
update counter

Counter representing the number of times the output data image
is transferred to the module's internal Master

98

99

Module PROFIBUS
input image data update
counter

Counter representing the number of times the input data image
is transferred from the module's internal Master

100

101

Module out mailbox
counter

Module out mailbox counter

102

103

Module in mailbox
counter

Module in mailbox counter

104

105

Module alarm IND
receive counter

Number of spontaneous alarm messages received from slave

106

107

Module alarm CON
receive counter

Number of confirmation messages received from slaves
indicating that the slave received the confirmation message
from the MVI56-PDPMV1 module

108

109

Reserved

110

111

Reserved

112

113

Module backplane read
count

Rollover counter of the number of MVI56-PDPMV1 to processor
backplane read data transfers

114

115

Module backplane write
count

Rollover counter of the number of MVI56-PDPMV1 to processor
backplane write data transfers

116

117

Module backplane error
count

Rollover counter of the number of MVI56-PDPMV1 to processor
backplane data transfers that have failed