ProSoft Technology MVI56-PDPMV1 User Manual

Page 57

Advertising
background image

MVI56-PDPMV1 ♦ ControlLogix Platform

Start Here

PROFIBUS DPV1 Master

User Manual

ProSoft Technology, Inc.

Page 57 of 255

March 22, 2011

3 Fill the module properties as required:

Parameter

Value

Name

Enter a module identification string. Example: MVI56PDPMV1_2

Description

Enter a description for the module. Example: ProSoft communication

module for PROFIBUS communication.

Comm Format

Select DATA-INT

Slot

Enter the slot number in the rack where the MVI56-PDPMV1 module is

located.

Input Assembly

Instance

1

Input Size

Enter the number of words per backplane input block to copy from the

module to the processor. The allowable range is from 12

TO

250 words.

Each input block will reserve 8 words for general purposes (CRC, block/CIP

handshaking). The remainder is reserved for PROFIBUS input data.

Output Assembly

Instance

2

Output Size

Enter the number of words per backplane output block to copy from the

module to the processor. The allowable range is from 5

TO

248 words. Each

output block will reserve 5 words for general purposes (CRC and block

handshaking). The remainder is reserved for PROFIBUS output data.

Configuration

Assembly Instance

4

Configuration Size

0

4 Click OK to confirm. The new module is now visible:

5 Expand the Tasks folder, and then expand the MainTask folder.
6 On the MainProgram folder, click the right mouse button to open a shortcut

menu. On the shortcut menu, choose N

EW

R

OUTINE

.

7 In the New Routine dialog box, enter the name and description of your

routine, and then click OK.

Advertising