ProSoft Technology MVI56-PDPMV1 User Manual
Page 39

MVI56-PDPMV1 ♦ ControlLogix Platform
Start Here
PROFIBUS DPV1 Master
User Manual
ProSoft Technology, Inc.
Page 39 of 255
March 22, 2011
IMPORTANT: ControlLogix Version 16 with FLEX Mode
If you change the connection sizes in the module profile, you must also update the following data
types with the new sizes. The connection I/O sizes defined in the module profile must always
match the following user-defined data types:
PDPMV1_C
ONNECTION
_I
NPUT
PDPMV1_C
ONNECTION
_O
UTPUT
You will also need to adjust limits in some of the ladder logic or AOI logic. For additional details,
see Adjusting the Connection Sizes for Your Application. (page 41)
The array sizes must be modified (in the Data Type column) to match the
connection sizes configured in the module profile. Failure to do so will prevent
the module from establishing backplane communication with the ControlLogix
processor.
Example 1
For the following example, if the module profile is configured as: