Mailbox Messaging

MVI56-PDPMV1 ♦ ControlLogix Platform

User Manual

PROFIBUS DPV1 Master

Page 172 of 255

ProSoft Technology, Inc.

March 22, 2011

Response:

 Message information (in response header)

"Invalid Data Size" is returned if Data size in the command header does not

equal 126.

If "Invalid Other" is returned, further information is to be found in Extended

word 8.

 Additional Fault information (Extended word 7)

If Extended word 8 equals 0x000A -"Failed to execute request" additional info

can be found here.

 Fault information (Extended word 8)

0x0001: Invalid setting in Message data word 1-63 of the command.

0x0002: At least one slave reports a warning. Refer to Message data word 1-

63.

0x000A: Failed to execute request. Additional fault information is to be found

in Extended word 7.

0x00FE: Command not possible; module operates as class 2 Master only.

0x00FF: Module not initialized (this command is only possible after

END_INIT).

 Message data word 1-63

Byte-array stating the status of the slaves. Array index is equal to slave

address.

0: Slave unaffected

1: Slave stopped

2: Warning - Slave could not be stopped because it is not part of the

configuration

3: Warning - Slave already stopped