Reference

MVI56-PDPMV1 ♦ ControlLogix Platform

User Manual

PROFIBUS DPV1 Master

Page 240 of 255

ProSoft Technology, Inc.

March 22, 2011

Byte Offset

Start

End

Name

Description

14

15

PROFIBUS Output Data size

The number of words to transfer from the processor in the
PROFIBUS output space during the output data transfer. Value
is selected during user configuration

16

17

Reserved

Reserved for future use

18

19

Reserved

Reserved for future use

20

21

Reserved

Reserved for future use

22

22

Input Data Byte Swap

User-configured flag to indicate if input data is swapped before
being placed in the input image for the controller.
0=No swapping
Not 0=Swap bytes

23

23

Output Data Byte Swap

User-configured flag to indicate if output data is swapped after
being received from the output image of the controller.
0=No swapping
Not 0=Swap bytes

24

24

Module software major version
number.

MVI56 module application software version number

Bits

16

8

7

0

High Byte

Low Byte

25

25

Module software minor version
number

26

41

PROFIBUS Slave Configured List

This is a 16-byte array with bit fields where one bit is assigned to
each slave station address. The associate bit is set if the slave
is present in the database. For the bit/slave relationship, refer to
the Slave List Structure below.

42

57

PROFIBUS Data Transfer Status

This is a 16-byte array with bit fields where one bit is assigned to
each slave station address. The associated bit is set if the slave
has reached or retained the "Data Exchange" state at least once
during the last three data cycles. For the bit/slave relationship,
refer to the Slave List Structure below.

58

73

PROFIBUS Slave Diagnostic
Status

This is a 16-byte array with bit fields where one bit is assigned to
each slave station address. When a slave leaves the "Deactive"
state for the first time, the associated bit is set. This bit is then
cleared when the slave enters "Data Exchange" state. If a slave
indicates "Extended Diagnostics" when it is in "Data Exchange"
state, the associated bit is set. For the bit/slave relationship,
refer to the Slave List Structure below.

Slave List Structure