MVI56-PDPMV1 ♦ ControlLogix Platform

Mailbox Messaging

PROFIBUS DPV1 Master

User Manual

ProSoft Technology, Inc.

Page 167 of 255

March 22, 2011

Seq Number
Unique identification number of the alarm. Range 0 to 31.

Alarm Spec Ack
Provides additional information about the alarm, such as if an error appears or

disappears. Also indicates whether the slave needs additional knowledge from

the Master. For example: writing to a certain memory area with an Acyclic Write

request.

Alarm Type
Identifies the alarm type such as Process Alarm, Plug Alarm, and so on. Range 1

to 6, 32 to 126.

Extended Diagnostic Flag
FFh: Slave sends an alarm message with "Extended Diag flag" set
00h: Slave sends an alarm message with "Extended Diag flag" cleared

Data [1 … n]
Additional manufacturer-specific alarm information (Alarm - PDU)

Fault Information
If the Message Information word in the header of the message indicates "Invalid

Other", addition information is available in this register.
3E00h: Module has received an invalid alarm indication data structure from a

DPV1 slave ("Slave Address" contains the node address of the slave that issued

the erroneous indication).
Refer to the PNO document "Extensions to EN50170 (DPV)" for more

information on how to interpret these parameters.

3.5.9 Mailbox Message: Set Operating Mode

This command allows setting the operating mode of the module (STOP, CLEAR,

or OPERATE).

Parameter

Description

Command Initiator

Application

Command Name

SET OPERATING MODE

Command Number

0200h

Fragmented

No

Extended Header Data

Fault information may be returned in the header of the response.