MVI56-PDPMV1 ♦ ControlLogix Platform

Configuring the MVI56-PDPMV1 Module

PROFIBUS DPV1 Master

User Manual

ProSoft Technology, Inc.

Page 129 of 255

March 22, 2011

2.5.4 Viewing the Controller Tags in RSLogix 5000

Note: For this procedure, you must connect a serial cable from the serial port on your PC to the
DB9M connector on the ControlLogix processor.


1 Open the sample ladder logic in RSLogix 5000.
2 Open the C

OMMUNICATIONS

menu, and choose G

O

O

NLINE

.

3 In the Controller Organization window, double-click C

ONTROLLER

T

AGS

.

4 Expand the MVI56PDPMV1, MVI56PDPMV1.Status and

MVI56PDPMV1.Status.Fieldbus tags.

Note: For the FLEX sample program, you must toggle the command bit
MVI56PDPMV1.Command.GetStatus in order to update the status data. For the LEGACY sample
program the status data is updated automatically.

In the illustration above, the binary value in

MVI56PDPMV1.Status.Fieldbus.FB_Slave_Cfg_List[15] indicates that a slave

is configured at address 125 (the PROFIBUS Slave Address configured in the

Slave Configuration (page 86) procedure).