MVI56-PDPMV1 ♦ ControlLogix Platform

Start Here

PROFIBUS DPV1 Master

User Manual

ProSoft Technology, Inc.

Page 71 of 255

March 22, 2011

1.8.4 Selecting the RPI Time for the Module

Refer to the Connection tab and enter the RPI time. The connection is scheduled

to move data to or from the module at least this often.
The RPI time to enter depends on your application as follows:

RPI Time 5 to 750 milliseconds
For ANY of the following conditions
 MVI56-PDPMV1 module firmware version 0.30
 MVI56-PDPMV1 module firmware version 1.21 (or later) AND configured in

LEGACY mode (U

SE

L

EGACY

M

ODE

=

Y

ES

)

 MVI56-PDPMV1 module firmware version 1.21 (or later) AND configured in

FLEX mode (U

SE

L

EGACY

M

ODE

= N

O

) AND MVI56-PDPMV1 is located in a

remote rack through ControlNet

Enter the RPI time that will provide optimum backplane performance for your

application, within the range from

5

MS

to 750

MS

.