ProSoft Technology MVI56-PDPMV1 User Manual

Page 232

Advertising
background image

Reference

MVI56-PDPMV1 ♦ ControlLogix Platform

User Manual

PROFIBUS DPV1 Master

Page 232 of 255

ProSoft Technology, Inc.

March 22, 2011

 Module configuration data values
 MVI56 software revision level
 Key PROFIBUS configuration values
 PROFIBUS Master hardware/software revision level
 MVI56 module statistics
 Mailbox messaging control and status
You can find the contents of the Status Data block in the MVI56PDPMV1.Status

user controller tag structure in RSLogix. These tags reference the
PDPMV1_Status user-defined data type.
The following table is received periodically from the MVI56 module.

Byte Offset

Start

End

Name

Description

0

9

Module ID string

Unique module 10-byte pattern as text "MVI5PDPMV1"

10

11

Reserved

Reserved for future use

12

13

PROFIBUS Input Data
size

The number of words of PROFIBUS input data to transfer from
the PROFIBUS Master to the processor within the Input Data
blocks. Value is selected during user configuration

14

15

PROFIBUS Output
Data size

The number of words to transfer from the processor in the
PROFIBUS output space during the output data transfer. Value
is selected during user configuration

16

17

Reserved

Reserved for future use

18

19

Reserved

Reserved for future use

20

21

Reserved

Reserved for future use

22

22

Input Data Byte Swap

User configured flag to indicate if input data is swapped before
being placed in the input image for the controller.
0=No swapping
Not 0=Swap bytes

23

23

Output Data Byte Swap User configured flag to indicate if output data is swapped after

being received from the output image of the controller.
0=No swapping
Not 0=Swap bytes

24

24

Module software major
version number.

MVI56 module application software version number

Bits

16

8

7

0

High Byte

Low Byte

25

25

Module software minor
version number

26

41

PROFIBUS Slave
Configured List

This is a 16-byte array with bit fields where one bit is assigned to
each slave station address. The associate bit is set if the slave is
present in the database. For the bit/slave relationship, refer to
the Slave List Structure below.

42

57

PROFIBUS Data
Transfer Status

This is a 16-byte array with bit fields where one bit is assigned to
each slave station address. The associated bit is set if the slave
has reached or retained the "Data Exchange" state at least once
during the last three data cycles. For the bit/slave relationship,
refer to the Slave List Structure below.