Configuring the MVI56-PDPMV1 Module

MVI56-PDPMV1 ♦ ControlLogix Platform

User Manual

PROFIBUS DPV1 Master

Page 112 of 255

ProSoft Technology, Inc.

March 22, 2011

3 Click CIP

P

ATH

E

DIT

to open the CIPconnect Path Editor dialog box.

The CIPconnect Path Editor allows you to define the path between the PC and

the MVI56-PDPMV1 module. The first connection from the PC is always the

1756-ENBT module (Ethernet/IP).
Each row corresponds to a physical rack in the CIP path.
 If the MVI56-PDPMV1 module is located in the same rack as the first 1756-

ENBT module, you should only set rack 1 and configure the associated

parameters.

 If the MVI56-PDPMV1 is available in a remote rack (accessible through

ControlNet or EtherNet/IP) then the user should include all racks (through the
A

DD

R

ACK

button).

Parameter

Description

Source Module

Source module type. This field is automatically selected
depending on the destination module of the last rack (1756-

CNB or 1756-ENBT).

Source Module IP Address

IP address of the source module (only applicable for 1756-

ENBT)

Source Module Node Address

Node address of the source module (only applicable for 1756-

CNB)

Destination Module

Select the destination module associated to the source module
in the rack. The connection between the source and destination

modules is performed through the backplane.

Destination Module Slot Number The slot number where the destination module is located.