MVI56-PDPMV1 ♦ ControlLogix Platform

Start Here

PROFIBUS DPV1 Master

User Manual

ProSoft Technology, Inc.

Page 47 of 255

March 22, 2011

Scenario 3: The PROFIBUS data fits into two backplane blocks (same PROFIBUS data count
per block)
For this example, we will split the PROFIBUS data evenly within two backplane

blocks, using the following backplane configuration:

For this scenario, each backplane block reserves 50 words for PROFIBUS I/O

data. The configured PROFIBUS I/O size (100 words) will not fit into one block,

so two backplane input blocks and two backplane output blocks will be required.

Backplane Block Overview

Block
Number

Input/
Output

Total word count
in backplane
block

PROFIBUS Data
Word Count in
backplane block

Initial PROFIBUS Data
Word Offset in
backplane block

Last PROFIBUS Data
Word Offset in
backplane block

1

Input

58

50

0

49

2

Input

58

50

50

99

1

Output

55

50

0

49

2

Output

55

50

50

99

Note: This configuration would be inefficient and is therefore not recommended. The first example
(Scenario 1) is a more efficient configuration that will accomplish the same thing. This example is
here solely to illustrate how changing the I/O sizes without changing the amount of PROFIBUS
data to be transferred will affect the number of I/O data blocks the module will need to transfer.