ProSoft Technology MVI56-PDPMV1 User Manual
Page 26
![background image](/files/866125/content/doc026.png)
Start Here
MVI56-PDPMV1 ♦ ControlLogix Platform
User Manual
PROFIBUS DPV1 Master
Page 26 of 255
ProSoft Technology, Inc.
March 22, 2011
2 Select the 1756-M
ODULE
(G
ENERIC
1756
M
ODULE
)
from the list and click OK.
This action opens the New Module dialog box.
3 Set the Module Properties values as follows:
Parameter
Value
Name
Enter a module identification string. Example:
MVI56PDPMV1
Description
Enter a description for the module. Example: ProSoft
communication module for PROFIBUS communication.
Comm Format
Select DATA-INT
Slot
Enter the slot number in the rack where the MVI56-
PDPMV1 module is located.
Input Assembly Instance
1
Input Size
250
Output Assembly Instance
2
Output Size
248
Configuration Assembly Instance
4
Configuration Size
0
4 On the Connection tab, set the RPI
value for your project. Click OK to
confirm.