ProSoft Technology MVI56-PDPMV1 User Manual

Page 131

Advertising
background image

MVI56-PDPMV1 ♦ ControlLogix Platform

Configuring the MVI56-PDPMV1 Module

PROFIBUS DPV1 Master

User Manual

ProSoft Technology, Inc.

Page 131 of 255

March 22, 2011

Note: The [Mailbox] string will only be available for the Legacy sample program. For the FLEX
sample program the controller tag is MVI56PDPMV1.Command.GetLiveList.

6 Next, expand the tag MVI56PDPMV1.Mailbox.GetLiveList.Station, to verify

that the MVI56-PDPMV1 responded to the GetLiveList message.
For MVI56PDPMV1.Mailbox.GetLiveList.Station[1] (the PROFIBUS Master

Address), notice that the value has changed from 4 (not communicating) to 3

(Master).

For MVI56PDPMV1.Mailbox.GetLiveList.Station[125] (the PROFIBUS Slave

Address configured in the Slave Configuration (page 86) procedure), notice

that the value has changed from 4 (not communicating) to 0 (Slave OK)