ProSoft Technology MVI56-PDPMV1 User Manual
Page 131

MVI56-PDPMV1 ♦ ControlLogix Platform
Configuring the MVI56-PDPMV1 Module
PROFIBUS DPV1 Master
User Manual
ProSoft Technology, Inc.
Page 131 of 255
March 22, 2011
Note: The [Mailbox] string will only be available for the Legacy sample program. For the FLEX
sample program the controller tag is MVI56PDPMV1.Command.GetLiveList.
6 Next, expand the tag MVI56PDPMV1.Mailbox.GetLiveList.Station, to verify
that the MVI56-PDPMV1 responded to the GetLiveList message.
For MVI56PDPMV1.Mailbox.GetLiveList.Station[1] (the PROFIBUS Master
Address), notice that the value has changed from 4 (not communicating) to 3
(Master).
For MVI56PDPMV1.Mailbox.GetLiveList.Station[125] (the PROFIBUS Slave
Address configured in the Slave Configuration (page 86) procedure), notice
that the value has changed from 4 (not communicating) to 0 (Slave OK)