ProSoft Technology MVI56-PDPMV1 User Manual

Page 18

Advertising
background image

Start Here

MVI56-PDPMV1 ♦ ControlLogix Platform

User Manual

PROFIBUS DPV1 Master

Page 18 of 255

ProSoft Technology, Inc.

March 22, 2011

1.5.2 Determining the Firmware Version of the MVI56-PDPMV1

Module

There are two ways to verify the module firmware version:

Checking the Version During Power-Up
When the module powers up, it will search for the ControlLogix processor to

establish backplane connectivity. If the correct ladder is not loaded to the

processor, or if the module is not located in the configured slot, or the processor

is missing, the module will not allow access to the debug menu and will print the

message "Waiting for Connection to the processor…"

Because debug menu access is not allowed at this point, view the debug menu

messages that are printed during power-up for the module firmware version.

Refer to the message that appears just before the message "C>pb_msts1":
If the message "MVI56-PDPMV1 Firmware Version = x.xx" appears on the

screen as shown in the following illustration, the module firmware is version 1.21

or later.