MVI56-PDPMV1 ♦ ControlLogix Platform

Reference

PROFIBUS DPV1 Master

User Manual

ProSoft Technology, Inc.

Page 239 of 255

March 22, 2011

Input Data Block (Block ID = 1 to n)
This block contains the previous input data received from the slaves.

Input Data Block Format (Input Image) (Local:1:I.Data Controller Tag)
You can find the contents of the Input Data Block (Input Image) in the
Local:1:I.Data user controller tags in RSLogix.

Word Offset

Start

End

Name

Description

0

0

Block Write ID

Block ID of the next write block to transfer from the processor to the
module

1

2

PROFIBUS CRC32 value

CRC32 checksum for PROFIBUS Master configuration downloaded
from configuration utility

3

4

Module CRC32 value

MVI56-PDPMV1 module configuration checksum for module
configuration downloaded from configuration utility

5

5

CIP Mailbox MSG Index

Latches bit 15 if new mailbox response is available

6

6

CIP Alarm MSG Index

Latches bit 15 if new alarm response is available

7

n-1

PROFIBUS Input Data

PROFIBUS input data transferred from the PROFIBUS slaves

n

n

Block Read ID

Block ID of this read block

MSG Status Data Details
The ControlLogix processor may periodically send a MSG request to retrieve the

status data from the MVI56-PDPMV1 module.
The types of data returned in the PROFIBUS Input Status area include:
 Module configuration data values
 MVI56 software revision level
 Key PROFIBUS configuration values
 PROFIBUS Master hardware/software revision level
 MVI56 module statistics
 Mailbox messaging control and status.
You can find the contents of the Status Data block in the MVI56PDPMV1.Status

user controller tag structure in RSLogix. These tags reference the

PDPMV1_Status user-defined data type.

The following table shows the data structure of the GetStatus mailbox response.

Byte Offset

Start

End

Name

Description

0

9

Module ID string

Unique module 10-byte pattern as text "MVI5PDPMV1"

10

11

Reserved

Reserved for future use

12

13

PROFIBUS Input Data size

The number of words of PROFIBUS input data to transfer from
the PROFIBUS Master to the processor within the Input Data
blocks. Value is selected during user configuration