Example:

To address Group 1, 2, and 4, the Group Select value should be D0h. If an

individual slave should be addressed, the correct group selection must also be

made, because the slave will ignore the message if it does not belong to the

requested group(s).
What group(s) a slave belongs to is determined during network configuration,

and is downloaded during initialization to each slave via the PROFIBUS telegram
Set_Prm.

Control Command
This parameter specifies the command to send:

Bit

Explanation

0 (LSB)

Reserved, set to zero

1

Reserved, set to zero

2

Unfreeze input data

3

Freeze input data

4

Unsynchronize output data

5

Synchronize output data

6

Reserved, set to zero

7 (MSB)

Reserved, set to zero

Combinations of the bits (Unsync/Sync and Unfreeze/Freeze)

Bits 0 or 6

Bits 1 or 7

Explanation

0

0

No function

0

1

Function will be activated

1

0

Function will be inactive

1

1

Function will be inactive

Fault Information and Extended Fault Information

"Fault Information" Contents

"Extended Fault Information" Contents

0100h

Address out of range -

0200h

Group number 0 not
permitted

-

0A00h

Failed to send Global

Control request

0A00h

Incorrect operation mode (Clear/Operate Only)

0150h

Invalid Freeze Group (Group is not initiated to be

Freeze Group)

0250h

Invalid Sync Group (Group is not initiated to be
Sync Group)

0350h

Incorrect Control Command

0450h

No Sync -/ or Freeze groups enabled in Master

configuration

FE00h

Command not

possible in Class 2
only mode

-

FF00h

Module not initialized -