ProSoft Technology MVI56-PDPMV1 User Manual

Page 163

Advertising
background image

MVI56-PDPMV1 ♦ ControlLogix Platform

Mailbox Messaging

PROFIBUS DPV1 Master

User Manual

ProSoft Technology, Inc.

Page 163 of 255

March 22, 2011

Length
This parameter specifies the number of bytes of the data block to read. If the

server data block length is less than requested, the length of the response will be

the actual length of the data block. If the server data block is greater or equal, the

response will contain the same amount of data.
The slave may answer with an error response if data access is not allowed.

Data [1 … n]
Returned data.

Fault Information and Extended Fault Information
If "Invalid Other" is returned in the Message Information word in the header of the

response, information about the fault can be found here.

"Fault Information"

"Extended Fault Information" Contents

0100h

Address out of range

-

0A00h

Failed to execute request

Refer to Return Codes (page 174).

0B00h Remote station failure
1000h

Remote station DPV1 failure

Function_Number

1100h

Length out of range (>240 bytes)

-

1200h

Slave does not support DPV1

-

1300h

Slave not active or not present in

configuration

-

FE00h

Command not possible in "Class 2-

Only" mode

-

FF00h

Module offline (not initialized or no

valid database)

-

Error Decode, Error Code 1 and Error Code 2
If "Fault Information" contains error code 1000h, more information according to

the DPV1 specification can be found here.