MVI56-PDPMV1 ♦ ControlLogix Platform

Diagnostics and Troubleshooting

PROFIBUS DPV1 Master

User Manual

ProSoft Technology, Inc.

Page 191 of 255

March 22, 2011

Viewing Input Data
Press [I] to open the Input Database View menu. Use this command to see the

contents of data placed in the Input database.

Viewing Output Data
Press [O] to open the Output Database menu. Use this command to see the

contents of data placed in the Output database.

Viewing Version Information
Press [V]

to view version information for the module.

Use this command to view the current version of the software for the module, as

well as other important values. You may be asked to provide this information

when calling for technical support on the product.
Values at the bottom of the display are important in determining module

operation. The Program Scan Counter value is incremented each time a

module’s program cycle is complete.

Tip: Repeat this command at one-second intervals to determine the frequency of program
execution.

Viewing Module Status
Press [1]

to view status information about the module. This screen also contains

useful information for mailbox troubleshooting:
 Scan count
 Mailbox counters
 Alarm counters
 Number of acyclic read and write operations performed by the module
You can also view the number of mailbox messages in the input and output

queues, and the number of alarms in the alarm queue.

Viewing PROFIBUS Data
Press [2] to view PROFIBUS data. Use this command to view information related
to the status of each slave in the PROFIBUS network, and to verify that each

slave is configured (SLAVE CFG LIST), exchanging data with the Master

(TRANSFER LIST) and in diagnostic mode (SLAVE DIAG LIST).
You can also check the module's operation state, where:
 00 = Offline
 40 = Stop
 80 = Clear
 C0 = Operate