ProSoft Technology MVI56-PDPMV1 User Manual

Page 51

Advertising
background image

MVI56-PDPMV1 ♦ ControlLogix Platform

Start Here

PROFIBUS DPV1 Master

User Manual

ProSoft Technology, Inc.

Page 51 of 255

March 22, 2011

3 Fill the module properties as follows:

Parameter

Value

Name

Enter a module identification string. Example: MVI56PDPMV1

Description

Enter a description for the module. Example: ProSoft communication

module for PROFIBUS communication.

Comm Format

Select DATA-INT

Slot

Enter the slot number in the rack where the MVI56-PDPMV1 module is

located.

Input Assembly

Instance

1

Input Size

Enter the number of words per backplane input block to copy from the
module to the processor. The allowable range is from 12 to 250 words.

Each input block will reserve 8 words for general purposes (CRC, block/CIP

handshaking). The remainder is reserved for PROFIBUS input data.

Output Assembly

Instance

2

Output Size

Enter the number of words per backplane output block to copy from the
module to the processor. The allowable range is from 5 to 248 words. Each
output block will reserve 5 words for general purposes (CRC and block

handshaking). The remainder is reserved for PROFIBUS output data.

Configuration

Assembly Instance

4

Configuration Size

0

4 The following illustration shows an example for a local rack application where

the module was set with the maximum backplane I/O sizes (250/248 words).

5 Click the C

ONNECTION

tab, and then enter the Requested Package Interval

(RPI) value.

o

If the module is located in the local rack (same rack where the processor

is located) or in a remote rack connected through EtherNet/IP adapters,

select the maximum value of 750

MS

.

o

If the module is located in a remote rack connected through ControlNet

adapters, adjust the RPI

time to be not less than 5

MS

and not less than

(and, preferably, some even multiple of) the RSNetWorx for ControlNet

Network Update Time (NUT).