ProSoft Technology MVI56-PDPMV1 User Manual

Page 182

Advertising
background image

Diagnostics and Troubleshooting

MVI56-PDPMV1 ♦ ControlLogix Platform

User Manual

PROFIBUS DPV1 Master

Page 182 of 255

ProSoft Technology, Inc.

March 22, 2011

The following tables will help you to troubleshoot different scenarios and the LED

behavior.

4.2.4 Legacy Mode (Use Legacy Mode = Yes)

Scenario

Debug Access After Power Up

LED Behavior After Power Up

- Module located in slot that is not
configured
OR
- No processor
OR
- Neither sample logics loaded to
processor (LEGACY or FLEX)

No
(Waiting for connection to
processor)

MSTR STAT= OFF
COM STAT=OFF
DBASE STAT=GREEN
TKN HLD= OFF
OK = RED
BP ACT = AMBER
APP STATUS= AMBER

LEGACY Ladder loaded to
processor (module is inserted in
configured slot)

Yes

MSTR STAT= GREEN
COM STAT= GREEN or OFF (depends if the
module is communicating with PROFIBUS
slaves)
DBASE STAT= GREEN
TKN HLD= GREEN
OK = GREEN
BP ACT = AMBER
APP STATUS= AMBER

FLEX Ladder

Yes

MSTR STAT= GREEN (1sec) /RED (2 secs)
COM STAT= OFF
DBASE STAT= GREEN
TKN HLD= GREEN
OK = GREEN
BP ACT = OFF
APP STATUS= AMBER

Advertising