Reference

MVI56-PDPMV1 ♦ ControlLogix Platform

User Manual

PROFIBUS DPV1 Master

Page 238 of 255

ProSoft Technology, Inc.

March 22, 2011

Word Offset

Start

End

Name

Description

1

1

Read Block Size
(MVI56PDPMV1.Util.ReadBlockSize)

Read block size (backplane connection input
length) as configured by the user through
RSLogix in the I/O Configuration section. The
size indicates the number of words to transfer
from the module to the processor at each
time.

2

2

Write Block Size
(MVI56PDPMV1.Util.WriteBlockSize)

Write block size (backplane connection
output length) as configured by the user
through RSLogix in the I/O Configuration
section. The size indicates the total number
of words to transfer from the processor to the
module at each time.

3

3

PROFIBUS Total Input Data Size
(MVI56PDPMV1.Config.PROFIBUS.InputDataSize)

PROFIBUS Input size configured in PCB
through the Input Data Size parameter.

4

4

PROFIBUS Total Output Data Size
(MVI56PDPMV1.Config.PROFIBUS.OutputDataSize)

PROFIBUS Output size configured in PCB
through the Output Data Size parameter.

5

5

Read Block Count
(MVI56PDPMV1.Util.ReadBlockCount)

Number of read blocks to transfer from the
module to the processor in order to transfer
the configured PROFIBUS input data.

6

6

Write Block Count
(MVI56PDPMV1.Util.WriteBlockCount)

Number of write blocks to transfer from the
processor to the module in order to transfer
the configured PROFIBUS output data.

7

7

PROFIBUS Input Data Word Count Per Read Block
(MVI56PDPMV1.Util.InputWordsPerReadBlock)

Maximum number of PROFIBUS input data
words that fit into one read block.

8

8

PROFIBUS Input Data Word Count Per Write Block
(MVI56PDPMV1.Util.OutputWordsPerWriteBlock)

Maximum number of PROFIBUS output data
words that fits into one write block.

9

9

PROFIBUS Input Data Word Count In Last Read Block
(MVI56PDPMV1.Util.InputWordsInLastReadBlock)

Number of PROFIBUS input data words in
the last read block. The last read block is the
one with highest block ID.

10

10

PROFIBUS Output Data Words In Last Write Block
(MVI56PDPMV1.Util.OutputWordsInLastWriteBlock)

Number of PROFIBUS output data words in
the last write block. The last write block is the
one with highest block ID.

11

11

Read Block ID

9990