MVI56-PDPMV1 ♦ ControlLogix Platform

Reference

PROFIBUS DPV1 Master

User Manual

ProSoft Technology, Inc.

Page 237 of 255

March 22, 2011

Block ID Numbers for Transfer

Block

Type

Description

0

Input Data

This block is generated only if the module has a single input block
(the configured PROFIBUS input data fits into one input backplane

block). It allows the switching between two blocks with different
block IDs but with same content. So in fact block 0 and block 1 will

transfer the same PROFIBUS input data.

1 to n

Input Data

Input data from PROFIBUS network with each block containing up

to 242 words of data (refer to Input Data Block (page 237))

1 to n

Output Data

Output data for PROFIBUS network with each block containing up

to 243 words of data (refer to Output Data Block (page 242))

Note: The maximum block count n will depend on the configured PROFIBUS I/O size and the
backplane block size for each application. For example, if the PROFIBUS input = 100 and each
backplane block will transfer 20 words of PROFIBUS data, then n=5.

Normal Operation
The MVI56-PDPMV1 module’s application code initiates the data transfers at the

end of every ControlLogix PLC ladder scan. As such, the MVI56-PDPMV1

module is able to actively read and write the PROFIBUS Cyclic Input/Output data

blocks in the appropriate locations.

Input Initialization Block (Block ID = 9990)
Block 9990 is the first block transferred by the module to the processor after one

of the following events:
 Module power up
 Module configuration through ProSoft Configuration Builder
 Module reboot
 ControlLogix mode switch from PROG to RUN
It contains general module configuration data, which allows the ladder logic to

correctly handle the handshaking between module and processor for proper

backplane communication.

Input Data Block Format (Input Image) (Local:1:I.Data Controller Tag)
You can find the contents of the Input Data Block (Input Image) in the
Local:1:I.Data user controller tags in RSLogix.

Word Offset

Start

End

Name

Description

0

0

Block Write ID

Block ID of the next write block. It will contain
a value of 9990 because the module expects
the next block from the processor to have the
same block ID.