Byte Offset

Start

End

Name

Description

110

111

Reserved

Reserved for future use

112

113

Module backplane read count

Rollover counter of the number of MVI56-PDPMV1 to processor
backplane read data transfers

114

115

Module backplane write count

Rollover counter of the number of MVI56-PDPMV1 to processor
backplane write data transfers

116

117

Module backplane error count

Rollover counter of the number of MVI56-PDPMV1 to processor
backplane data transfers that have failed

118

119

File Error Word

Bitmapped value that indicates which files are not present
Bit 0: Problem with PDPMV1.CFG file
Bit 1: Not used
Bit 2: Problem with PDPMV1.DDB file
Bit 3: Problem with PDPMV1.XML file
Bits 4 to 15 not used.
If this word has a value other than 0, the CFG ERR LED on the
module will be illuminated.

120

145

Reserved

Reserved for future use

146

147

In mailbox queue count

Number of message in the in mailbox queue

148

149

Out mailbox queue count

Number of message in the out mailbox queue

150

151

Alarm queue count

Number of message in the alarm queue

152

153

Last out mailbox message ID
processed from output image

Last out mailbox message ID processed from output image

154

155

Current in mailbox control index

Current in mailbox control index

156

157

Current alarm control index

Current alarm control index

158

496

Reserved for future use

496

497

Index of Output image to receive (1 to 4 for data, 0 or -1 if no
data)

498

499

Block index of -1 or 0 for status block

Output Data Block (Block ID = 1 to n)
This block contains the PROFIBUS output data to be sent from the processor to

the module.

Output Data Block Format (Output Image)
You can find the contents of the Output Data Block (Output Image) in the
MVI56PDPMV1.Output user controller tags in RSLogix.

Byte Offset

Start

End

Name

Description

0

0

Write Block ID

Block number of this write block 1 to n

1

2

PROFIBUS CRC32 value

Computed for PROFIBUS Config

Advertising