Standard PROFIBUS Slave Diagnostic Bytes
The diagnostic information consists of 6 bytes of standard diagnostic information

plus any user-related diagnostic information. The standard information is shown

in the tables below.

Byte

Description

0

Station status 1

1

Station status 2

2

Station status 3

3

Master address

4

Ident number high

5

Ident number low

Byte 0 - Station Status 1 Bits

Bit

Description

0

Station not existent

1

Station not ready

2

Configuration fault

3

Extended diagnostic data present

4

Not supported

5

Invalid slave response

6

Parameter fault

7

Master lock

Byte 1 - Station Status 2 Bits

Bit

Description

0

Parameter request

1

Static diagnostic

2

Slave device

3

Watchdog on

4

Freeze mode

5

Sync mode

6

Reserved

7

Slave deactivated