L-force | PLC Designer - SoftMotion

The SoftMotion drive interface

Control configuration for SoftMotion

Parameters of the PLC configuration

The following parameters can be viewed and altered under the Module parameters tab.

Parameter

Description

wParam1

CAN channel no. (typically 0)

wParam2

Baud rate in kBit (125, 250, 500, 1000)

wParam3

Sync generator:

0: The PLC generates the sync signal (only possible if the PLC has a high precision)

1: The 1. drive in the AxisGroup generates the sync signal

2: A sync device generates the sync signal (additional hardware required)

wParam4

Not used

dwParam1

Reserved

dwParam2

Reserved

dwParam3

Not used

dwParam4

Reserved

Parameter

Description

sTask

String that corresponds to the name of the task in which the data transmission of this

axis group is to take place.

dwCycle

Cycle time of the task defined under "sTask" in μs

(only has to be specified if the control system does not support any tasks and

automatically calls PLC_PRG (default task))

wParam1

...

wParam4

Card/drive-specific parameters of the WORD type

dwParam1

...

dwParam4

Card/drive-specific parameters of the DWORD type