3 candrive, Candrive, Candrive ( 22) – Lenze PLC Designer PLC-Designer (R2-x) SoftMotion User Manual

Page 22

Advertising
background image

L-force | PLC Designer - SoftMotion

The SoftMotion drive interface

Control configuration for SoftMotion

22

L

DMS 5.2 EN 03/2011 TD17

3.1.3

CANDrive

In this dialog the drive ID (Drive ID) is defined. Furthermore the drive type is selected: linear

or rotary (modulo).
In the Conversion factor area the conversion between the integer position values received

by the drive (first line on the left) and the technical units used in the IEC program (first line

on the right) is defined. Set the value 65536 in the Increments input field. Here also a

gearbox can be taken into consideration (second and third line). In the above example a

drive would exactly carry out a mechanical revolution if 360 degrees were programmed.
Depending on the drive type selected, software limit switches can be defined in the area

Settings for linear drive for linear drives, or the modulo range has to be defined for rotary

drives.
In the cyclic communication data area is it selected which setpoint and actual data are to

be transmitted cyclically between the control system (PLC) and the drive.

Under Maximum values the limit values are set which are used by SMC_ControlBy blocks

to determine whether there is a skip (see

SMC_ControlAxisByPos

( 38)

).

Note!

ECSxM (motion) Lenze controllers only support the transmission of position

values in the cyclic communication data. If these controllers are used, therefore

no further cyclic data must be activated.

Advertising