Pulse in scale, Encoder ppr, Frequency set – Rockwell Automation 1336F PLUS II User Manual - Firmware 1.xxx-6.xxx User Manual
Page 100
6–18
Programming
[Pulse In Scale]
Provides a scaling factor for the pulse input.
Example:
4 Pole Motor, 60 Hz = Max. Speed.
The 1336-MOD-N1 option outputs 64 Hz/Hz. At full analog
reference, the pulse input to the drive will be 60 Hz x 64
Hz/Hz = 3840 pulses/sec.
Parameter Number
264
Parameter Type
Read and Write
Display Units / Drive Units
Factor / Pulses per Rev
Factory Default
64 PPR
Minimum Value
1
Maximum Value
4096
[Encoder PPR]
This parameter sets the scaling for encoder feedback
speed regulation. Enter the actual encoder pulses per
revolution
Parameter Number
46
Parameter Type
Read and Write
Display Units / Drive Units
Factor / Pulses per Rev
Factory Default
1024 PPR
Minimum Value
1
Maximum Value
4096
Scale
Factor
Incoming Pulse Rate (Hz)
Desired Command Freq.
=
Scale Factor =
3840 Hz
60 Hz
= 64