Frequency Set

[Pulse In Scale]

Provides a scaling factor for the pulse input.

Example:
4 Pole Motor, 60 Hz = Max. Speed.
The 1336-MOD-N1 option outputs 64 Hz/Hz. At full analog
reference, the pulse input to the drive will be 60 Hz x 64
Hz/Hz = 3840 pulses/sec.

Parameter Number

264

Parameter Type

Read and Write

Display Units / Drive Units

Factor / Pulses per Rev

Factory Default

64 PPR

Minimum Value

1

Maximum Value

4096

[Encoder PPR]

This parameter sets the scaling for encoder feedback
speed regulation. Enter the actual encoder pulses per
revolution

Parameter Number

46

Parameter Type

Read and Write

Display Units / Drive Units

Factor / Pulses per Rev

Factory Default

1024 PPR

Minimum Value

1

Maximum Value

4096

Scale

Factor

Incoming Pulse Rate (Hz)

Desired Command Freq.

=

Scale Factor =

3840 Hz

60 Hz

= 64