Fault alarms 2, Flt clear mode, Ground warning – Rockwell Automation 1336F PLUS II User Manual - Firmware 1.xxx-6.xxx User Manual

Page 117: Phase loss mode, Phase loss level, Precharge fault, Motor ol ret, Faults

Advertising
background image

Programming

6–35

Faults

[Fault Alarms 2]

This parameter stores and displays the
last alarm conditions present prior to a
fault. Refer to Chapter 7 for further alarm
information.

A Status description (bit ENUM) is
displayed on line 1 (except Series A
HIMs below version 3.0).

Parameter Number

287

Parameter Type

Read Only

[Flt Clear Mode]

This parameter controls the method for clearing faults.

Parameter Number

39

Parameter Type

Read and Write

Factory Default

“Enabled”

Units

Display Drive

“Disabled” 0

Faults cleared only by cycling power

“Enabled” 1

Faults cleared by issuing a valid stop
command (only through TB3/HIM) or
cycling power - see Bit 3 of the Logic
Control Structure in Appendix A.

[Ground Warning]

Enables the Ground Warning fault (F57) when the drive
senses ground current in excess of 2 amperes (approxi-
mate). Refer to Chapter 7 for further information.

Parameter Number

204

Parameter Type

Read and Write

Factory Default

“Disabled”

Units

Display Drive

“Disabled” 0

No Fault Generated

“Enabled” 1

Ground Warning Generated

[Phase Loss Mode]

Enables the function that detects a phase loss or the
current rating has been exceeded in the drive if powered
on single-phase line. A fault (F49) or alarm condition will
occur if the DC bus ripple voltage exceeds the level in
[Phase Loss Level].

Parameter Number

330

Parameter Type

Read and Write

Factory Default

“Disabled”

Units

Display Drive

“Disabled” 0

No Fault Generated

“Alarm” 1

Generates a Phase Loss Alarm

“Fault” 2

Generated F49 Input Phase Fault

[Phase Loss Level]

Sets the DC bus ripple voltage above which a phase loss
fault/alarm will occur. The sensitivity for detecting a blown
fuse on a three-phase system can be increased by
lowering the setting for this parameter.

Parameter Number

331

Parameter Type

Read and Write

Display Units / Drive Units

0.1 Volts / 4096 = Drive Rtd Volts

Factory Default

9.0/18.0/22.5 Volts

12.4/24.7/30.9 Volts

Firmware 6.001 & later

Minimum Value

5.1/10.1/12.7 Volts

Maximum Value

22.5/45.0/56.2 Volts

45.0/90.0/112.5 Volts

Firmware 6.001 & later

[Precharge Fault]

Enables or disables the Precharge Fault, which indicates
insufficient DC bus charging 20 seconds after power-up.

Parameter Number

332

Parameter Type

Read and Write

Factory Default

“Enabled”

Units

Display Drive

“Disabled” 0

No Fault Generated

“Enabled” 1

Precharge Fault Generated

[Motor OL Ret]

– Firmware 6.001 & later

When enabled, the accumulated motor overload count will
be stored on power-down and restored on power-up. From
that point, normal overload operation continues. When the
value is changed from enabled to disabled the motor
overload count will be reset to 0.

Parameter Number

379

Parameter Type

Read and Write

Factory Default

“Disabled”

Units

Display Drive

“Disabled” 0

Motor OL count not saved

“Enabled” 1

Motor OL count saved on power-
down and restored on power-up

Motor Therm

Bit 15

Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7

Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0

Bit 14

Unused

Encoder Loss

Load Loss

Enc Cnt Max

Enc Cnt Set

Voltage Check