[Freq Source]

This parameter displays the frequency source currently
commanding the drive.

Parameter Number

62

Parameter Type

Read Only

Factory Default

“Use Last”

Units

Display Drive

“Use Last” 0

“Analog In 0” 1
“Analog In 1” 2
“Analog In 2” 3

“Pulse Ref” 4

Refer to [Pulse In Scale] Value

“MOP” 5

“Adapter 1-6” 6-11

“Preset 1-7” 12-18

“Encoder” 19 Refer to [Encoder PPR] Value

Firmware 5.001 & later

“Step Logic” 20

“Jog Sel” 20 “21” in Firmware 5.001 & later

“AutoTune Ref” 21 “22” in Firmware 5.001 & later

[Freq Command]

This parameter displays the frequency that the drive is
commanded to output. This command may come from any
one of the frequency sources selected by [Freq Select 1]
or [Freq Select 2].

Parameter Number

65

Parameter Type

Read Only

Display Units / Drive Units

0.01 Hertz / 32767 = Maximum Freq Forward

Factory Default

None

Minimum Value

–400.00 Hz

Maximum Value

+400.00 Hz

[Drive Direction]

This parameter displays the commanded running
direction.

Parameter Number

69

Parameter Type

Read and Write

Factory Default

None

Units

Display Drive

“Forward” 0

“Reverse” 1

[Stop Mode Used]

This parameter displays the active stop mode.

Parameter Number

26

Parameter Type

Read Only

Factory Default

“Coast”

Units

Display Drive
“Coast” 0

See [Stop Select 1] on page

6–9

“DC Brake” 1

See [Stop Select 1] on page

6–9

“Ramp” 2

See [Stop Select 1] on page

6–9

“S Curve” 3

See [Stop Select 1] on page

6–9

“Ramp to Hold” 4

See [Stop Select 1] on page

6–9

[Motor Mode]

This parameter displays the motor mode.

Parameter Number

141

Parameter Type

Read Only

Factory Default

None

Units

Display Drive

“1” 1

Power up sequence in progress

“2” 2

Motor connected, drive off

“3” 3

DC boost being applied

“4” 4

Motor running at [Dwell Frequency]

“5” 5

Motor accelerating

“6” 6

Motor at command speed

“7” 7

Motor decelerating

“8” 8

Motor coasting

“9” 9

Motor under DC braking

“10” 10 Waiting for fault reset - returns to 0
“11” 11 Start mode
“12” 12 Flying start search enable
“13” 13 Flying start w/encoder in process