Optional analog i/o configurations, Optional analog i/o configurations –34, Option board installation/removal – Rockwell Automation 1336F PLUS II User Manual - Firmware 1.xxx-6.xxx User Manual

Page 44: Option board setup

Advertising
background image

2–34

Installation/Wiring

Optional Analog I/O
Configurations

If your drive was received with Analog Options (LA1, LA2, etc.)
factory installed, the boards must be setup before use. Proceed to
Option Board Setup” below.

Option Board Installation/Removal

If the drive is not factory configured with Analog Options, the desired
option boards can be user installed. Prior to installation, the jumpers
at J9 and/or J10 must be removed. If a board is removed at a later
time, the jumpers must be reinstalled. Refer to the detailed instruc-
tions supplied with the option boards.

Important:

Drive power must be removed prior to jumper installation/
removal.

Option Board Setup

Before operation, each installed option board must configured. The
board will have one or two DIP switches depending on the option
selected. The first function (input or output) is configured with the S1
DIP switch – the second function (if present) is configured with S51.
Using the table below, set the switch(es) for correct operation.

Important:

Due to different switch manufacturers, the individual
switches will be designated “A or 1” and “B or 2.” In
addition, switch positions will be indicated as “Off or 0”
and “On or 1.”

S1 and S51 Configuration Settings

Option

DIP Switch S1

DIP Switch S51

Function Mode

Switch Setting

Function Mode

Switch Setting

A/1

B/2

A/1

B/2

LA1

Output 0 10V

Off/“0”

Off/“0”

Configure Standard Analog Input 2 with J11.
See page

2–33

for further information.

20mA On/“1”

On/“1”

LA2

Input 0

10V

Off/“0”

On/“1”

Input 1

10V

Off/“0”

On/“1”

20mA On/“1”

Off/“0”

20mA On/“1”

Off/“0”

LA3

Output 0 10V

Off/“0”

Off/“0”

Output 1 10V

Off/“0”

Off/“0”

20mA On/“1”

On/“1”

20mA On/“1”

On/“1”

LA4

Input 2

10V

Off/“0”

On/“1”

Output 1 10V

Off/“0”

Off/“0”

20mA On/“1”

Off/“0”

20mA On/“1”

On/“1”

LA5

Output 0 10V

Off/“0”

Off/“0”

20mA On/“1”

On/“1”

LA6

Input 0

10V

Off/“0”

On/“1”

20mA On/“1”

Off/“0”

LA7

Input 0

10V

Off/“0”

On/“1”

Input 1

10V

Off/“0”

On/“1”

20mA On/“1”

Off/“0”

20mA On/“1”

Off/“0”

1

2

On / 1 =

Off / 0 =

Switches S1 and S51

Advertising