Start-Up

5–3

Reset Factory Defaults

3. Important: The remaining steps in this procedure are based on factory default

parameter settings. If the drive has been previously operated, parameter
settings may have been changed and may not be compatible with this start-up
procedure or application. Drive status and fault conditions may be unpredict-
able when power is first applied.

To obtain proper results, the parameters must be restored to factory default
settings.

A. From the Status Display, press Enter (or any key). “Choose Mode” will be

displayed.

B. Press the Increment (or Decrement) key until “EEPROM” is displayed. If

EEProm is not in the menu, programming is password protected. Refer to
Chapter 3 for Password information.

C. Press Enter.

D. Press the Increment (or Decrement) key until “Reset Defaults” is displayed.

E. Press Enter to restore all parameters to their original factory settings.

F.

Press ESC. “Reprogram Fault” will display, indicating successful reset.

G. Press the Stop key to reset the fault. Cycle power.

Choose Mode

Display

Choose Mode

EEProm

EEProm

Reset Defaults

Choose Mode

EEProm

Reprogram Fault

F48

Stopped

+0.00 Hz

4. From the Status Display, press the Enter key (or any key). “Choose Mode” will

be displayed.

A. Press the Increment (or Decrement) key until “Startup” is displayed.

B. Press Enter.

Important: All questions can be answered Yes or No. Pressing Enter will
select the default (“Y” or “N”). Pressing the Increment (or Decrement) key will
change the selection – press Enter to select. Choosing “Y” allows you to pro-
ceed through the step, “No” will advance you to the next step. In addition, the
following should be noted:

The “Startup” mode can be exited at any time by pressing ESCape until the
Status Display is shown. If you wish to re-enter the “Startup” mode, simply
select “Reset Sequence” to start from the beginning. Selecting “Continue”
allows you to resume from the point where you left off.

Completing the last action in any step will automatically take you to the next
step.

Pressing SELect will activate line 2 of the display – this must be done for
all values.

Press the Increment (or Decrement) key to adjust a value (skip if value is
correct). Press Enter to store the value or retain the existing value. Pressing
Enter again will cause you to move to the next step (parameter).

Choose Mode

Display

Choose Mode

Startup

Assisted Start-Up

Keys

Description

The HIM Display will show . . .

or

or

or

or