6–24

Programming

Feature Select

[Line Loss Volts]

Sets the bus voltage below which the drive recognizes a
line loss. Specifically: If [DC Bus Voltage] drops below
[DC Bus Memory] – [Line Loss Volts] and if [Line Loss
Mode] is set to 0 or 2, the [Drive Alarm 1]. Line Loss bit
will be set and the drive will take the selected line loss
action.

Parameter Number

320

Parameter Type

Read and Write

Display Units / Drive Units

1 Volt / 4096 = Drive Rtd Volts

Factory Default

59/117/146 Volts

Minimum Value

40/80/100 Volts

Maximum Value

200/400/500 Volts

[Loss Recover]

Sets the bus voltage above which the drive recognizes a
line loss recovery. Specifically: If [DC Bus Voltage] rises
above [DC Bus Memory] – [Loss Recover] and if [Line
Loss Mode] is set to 0 or 2, the “Line Loss” bit of [Drive
Alarm 1] is cleared and the drive recovers from line loss.
This parameter should be set lower than [Line Loss Volts]
(i.e. for a higher bus voltage), otherwise the drive will cycle
in and out of line loss.

Parameter Number

321

Parameter Type

Read and Write

Display Units / Drive Units

1 Volt / 4096 = Drive Rtd Volts

Factory Default

29/59/73 Volts

Minimum Value

20/40/50 Volts

Maximum Value

200/400/500 Volts

[Ride Thru Volts]

Sets the bus voltage that the inertia ride thru function will
attempt to regulate. If [Line Loss Mode] = “LoBus>Decel,”
a line loss condition activates the inertia ride thru function.
The load is decelerated such that the energy absorbed
from the mechanical load balances the losses – bus
voltage is maintained.

This parameter should be set greater than [Loss Recover]
(i.e. for a lower bus voltage). Otherwise the drive will cycle
in and out of line loss.

NOTE: If [Line Loss Mode] = “Input>Decel,” line loss
operation is similar but the inertia ride thru function
regulates the bus to the value in [DC Bus Memory].

Parameter Number

322

Parameter Type

Read and Write

Display Units / Drive Units

1 Volt / 4096 = Drive Rtd Volts

Factory Default

29/59/73 Volts

Minimum Value

40/80/100 Volts

Maximum Value

200/400/500 Volts

[Min Bus Volts]

Sets the bus voltage below which the drive will disable
firing. The “Line Loss” flag in [Drive Alarm 1] is always set.
If [Low Bus Fault] = “Enabled” the drive faults with an F04
“Undervolt Fault.” This means that even if [Line Loss
Mode] = “Input>Decel” dropping below minimum bus
disables firing and signals a line loss.:

To check the minimum safe value for [Minimum Bus]:

- Set [Low Bus Fault] = “Disabled”.

- Set [Line Loss Fault] = “Disabled”.

- Select [DC Bus Voltage] on the HIM.

- With the drive stopped, disconnect power from the

drive.

- Watch the HIM display for the lowest voltage reading

before the HIM loses power.

Parameter Number

323

Parameter Type

Read and Write

Display Units / Drive Units

1 Volt / 4096 = Drive Rtd Volts

Factory Default

194/388/485 Volts

Minimum Value

100/200/250 Volts

Maximum Value

200/400/500 Volts

[Traverse Inc]

Sets the time period of increasing frequency. Setting this
parameter to zero disables the P Jump function.

Parameter Number

78

Parameter Type

Read and Write

Display Units / Drive Units

0.01 Second / Seconds x 100

Factory Default

0.00 Sec

Minimum Value

0.00 Sec

Maximum Value

30.00 Sec

ATTENTION: To guard against possible drive damage, this parameter MUST
be set such that firing is disabled at a bus voltage higher than the bus voltage
at which the power supply for the gate drive circuits is lost. See the procedure
at left to check the minimum value for this parameter.

!