Alarms, Alarms –9 – Rockwell Automation 1336F PLUS II User Manual - Firmware 1.xxx-6.xxx User Manual

Page 155

Advertising
background image

Troubleshooting

7–9

Alarms

Table 7.D

presents a listing and description of the drive alarms. Alarm

status can be viewed by selecting the [Drive Alarm 1/2] parameter.
An active alarm will be indicated by its corresponding bit being set to
high (1). Any high bit (1) can energize CR1-4 (if programmed).

Table 7.D
Alarm Conditions

Parameter Name [Drive Alarm 1]

Parameter Number 60

Parameter Type

Read Only

Parameter Name [Drive Alarm 2]

Parameter Number 269

Parameter Type

Read Only

Bus Charging

Regenerating Current Limit

Regenerating Voltage Limit

Line Loss In Progress

Motor Stalled

Ground Warning

Bit 15

Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0

Mtr Overload

Sync Loss

Bit 14

Hardware Current Limit

Motoring Current Limit

Motor OL Trip

Auto Reset

Phase Loss

Heatsink Temp

Auxiliary Input

4-20 mA Loss

Motor Therm

Bit 15

Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7

Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0

Bit 14

Unused

Encoder Loss

Load Loss

Enc Cnt Max

Enc Cnt Set

Voltage Check

Alarm

Bit

Alarm Name

Description

[Drive
Alarm 1]

0

Bus Charging

Precharge of DC bus capacitors is in progress.

1

Hardware Current Limit

An alarm will be issued when 220% of drive rated current is reached.

2

Motoring Current Limit

The value programmed for [Current Limit] has been exceeded while in the motoring mode.

3

Regenerating Current Limit An alarm will be issued when the value set for [Current Limit] has been exceeded while the motor is

regenerating.

4

Regenerating Voltage Limit Bus limiting is active.

5

Line Loss In Progress

An alarm will be issued when the AC incoming voltage drops below 20% of input or a 150 volt drop
takes place.

6

Mtr Overload

At the present value of output amps, a motor overload trip will eventually occur.

7

Motor Stalled

Drive output frequency folds to 0 Hz and current limit is still active or voltage limit will not allow decel.

8

Ground Warning

Ground current exceeds 2 amperes.

9

Auxiliary Input

Input circuit is open.

10

Heatsink Temp

Temperature of drive heatsink has exceeded its limit.

11

Sync Loss

Synchronous motor not at synchronous speed.

12

Phase Loss

The DC bus ripple has exceeded the level in [Phase Loss Level].

13

4-20mA Loss

4-20mA signal lost.

14

Motor OL Trip

This bit will be high when the motor overload function has integrated high enough to cause a motor
overload fault. This bit is active regardless of the [Motor Overload] state (enabled/disabled).

15

Auto Reset

Drive is attempting to reset a fault using [Reset/Run Tries] & [Reset/Run Time].