Step logic – Rockwell Automation 1336F PLUS II User Manual - Firmware 1.xxx-6.xxx User Manual

Page 143

Advertising
background image

Programming

6–61

StepLogic™ offers a degree of PLC functionality for simple applica-
tions. It consists of 7 frequency steps which can be stepped through
based on a number of factors. The frequency steps are programmed
into the [Preset Freq x] parameters (x = Current Step + 1). Each step
also has a time associated with it, [SLx Time]. The logic for each step
is defined by four StepLogic parameters.

• [SLx Logic Step] – if true, will move the program to the next step.

• [SLx Logic Jump] – if true, will jump to the step defined in [SL

Step Jump].

• [SL Step Jump] – if both [SLx Logic Step] and [SLx Logic Jump]

are true, the program will jump to the step defined in this parame-
ter. [SLx Logic Jump] takes precedence over [SLx Logic Step].

• [SLx Step Setting] – sets 4 functions of the step. Refer to the

parameter description on page

6–63

.

A valid Start command will cause the program to run and continue to
loop unless one of the steps causes the program to end, a Stop com-
mand is given or the Enable is opened. When the Enable is opened in
2-wire control, the drive will stop. When closed, the drive will restart
at the last step, if the Start is still closed. Note that in order to move to
a different step based on digital inputs, at least one input must change
state since the last step.

See Example below and

Figure 6.1

.

Step

Logic

The Step Logic Parameters are only available with Firmware versions 5.001 and later.

No.

Parameter

Setting

No.

Parameter

Setting

5

Freq Select 1

Step Logic

351

SL2 Time

0.00

158

CR1 Out Select

Step Logic

352

SL2 Encoder Cnts

0

242

TB3 Term 22 Sel

SL Input 1

353

SL3 Logic Step

Step on Time

243

TB3 Term 23 Sel

SL Input 2

354

SL3 Logic Jump

SL2 not SL1

27

Preset Freq 1

20 (SL0)

355

SL3 Step Jump

End Fault

28

Preset Freq 2

10 (SL1)

356

SL3 Step Setting

0111

29

Preset Freq 3

20 (SL2)

357

SL3 Time

0.00

30

Preset Freq 4

30 (SL3)

358

SL3 Encoder Cnts

-10

31

Preset Freq 5

40 (SL4)

359

SL4 Logic Step

All SL True

32

Preset Freq 6

50 (SL5)

360

SL4 Logic Jump

Do Not Step

33

Preset Freq 7

60 (SL6)

361

SL4 Step Jump

Jump to 2

335

SL0 Logic Step

SL1 In True

362

SL4 Step Setting

0001

336

SL0 Logic Jump

SL2 In True

363

SL4 Time

0.00

337

SL0 Step Jump

Jump to 2

364

SL4 Encoder Cnts

0

338

SL0 Step Setting

0000

365

SL5 Logic Step

Time and SL1

339

SL0 Time

0.00

366

SL5 Logic Jump

SL2 In True

340

SL0 Encoder Cnts

0

367

SL5 Step Jump

End Stop 2

341

SL1 Logic Step

SL1 In True

368

SL5 Step Setting

1110

342

SL1 Logic Jump

Time and SL2

369

SL5 Time

0.00

343

SL1 Step Jump

Jump to 3

370

SL5 Encoder Cnts

15

344

SL1 Step Setting

0100

371

SL6 Logic Step

SL1 In True

345

SL1 Time

10.00

372

SL6 Logic Jump

SL2 In False

346

SL1 Encoder Cnts

0

373

SL6 Step Jump

End Stop 1

347

SL2 Logic Step

All SL True

374

SL6 Step Setting

0000

348

SL2 Logic Jump

SL2 In True

375

SL6 Time

0.00

349

SL2 Step Jump

Jump to 6

376

SL6 Encoder Cnts

0

350

SL2 Step Setting

0001

Advertising