Installation/Wiring

2–31

Pulse Input/Output Option

Pulse Input

The pulse input signal must be an externally powered square-wave
pulse at a 5V TTL logic level. As measured at the terminal block,
circuits in the high state must generate a voltage between 3.6 and
5.5V DC at 8 mA. Circuits in the low state must generate a voltage
between 0.0 and 0.8V DC. Maximum input frequency is 250kHz.
Scale factor [Pulse/Enc Scale] must be set.

Pulse Output

Provides a TTL pulse train suitable for driving up to three
1336

PLUS

II

pulse inputs or a separate 125 ohm load at TTL levels

(4V at 32 mA source, 0.8V at 3.2 mA sink).

Digital Outputs

The digital outputs are at terminals 10 through 18 of TB2.

Figure 2.5
Digital Outputs – TB2

!

ATTENTION: If input voltages are maintained at levels
above

±12V DC, signals may be degraded and component

damage may result.

Only Present

on B Frame

& Up Drives

Reserved for

Future Use

CR2

CR1

CR3

CR3

CR4

CR4

10

11

12

13

14

15

16

17

18

A1

A2

Terminal
TE
10, 11
11, 12
13, 14
14, 15
16, 17
17, 18
A1, A2

Signal
True Earth - Shield Termination
CR1 Programmable Contact
CR2 Programmable Contact

CR3 Programmable Contact

CR4 Programmable Contact

Reserved for Future Use

Resistive Rating = 115V AC/30V DC, 5.0A
Inductive Rating = 115V AC/30V DC, 2.0A

Important: On A Frame drives, the power supply used for relay contact outputs

requires a field installation at the supply source of transient voltage surge
suppression with maximum clamping voltage of 2.5 kV.

Any relay programmed as Fault or Alarm will energize (pick up) when power is applied
to drive and deenergize (drop out) when a fault or alarm exists. Relays selected for
other functions will energize only when that condition exists and will deenergize when
condition is removed.