Frequency set, Freq select 1, Freq select 2 – Rockwell Automation 1336F PLUS II User Manual - Firmware 1.xxx-6.xxx User Manual

Page 98: Jog frequency

Advertising
background image

6–16

Programming

Frequency

Set

This group of parameters contains internally stored frequency settings.

[Freq Select 1]

This parameter controls which of the frequency sources
is currently supplying the [Freq Command] to the drive
unless [Freq Select 2] or [Preset Freq 1-7] is selected.
Refer to the Speed Select Input table in Chapter 2.

Parameter Number

5

Parameter Type

Read and Write

Factory Default

“Adapter 1”

Units

Display Drive

“Use Last” 0

“Analog In 0” 1
“Analog In 1” 2
“Analog In 2” 3

“Pulse Ref” 4

Refer to [Pulse In Scale] Value

“MOP” 5

“Adapter 1-6” 6-11

“Preset 1-7” 12-18

“Encoder” 19 Refer to [Encoder PPR] Value

Firmware 5.001 & later

“Step Logic” 20

[Freq Select 2]

This parameter controls which of the frequency sources
is currently supplying the [Freq Command] to the drive
unless [Freq Select 1] or [Preset Freq 1-7] is selected.
Refer to the Speed Select Input table in Chapter 2.

Parameter Number

6

Parameter Type

Read and Write

Factory Default

“Preset 1”

Units

Display Drive

“Use Last” 0

“Analog In 0” 1
“Analog In 1” 2
“Analog In 2” 3

“Pulse Ref” 4

Refer to [Pulse In Scale] Value

“MOP” 5

“Adapter 1-6” 6-11

“Preset 1-7” 12-18

“Encoder” 19 Refer to [Encoder PPR] Value

Firmware 5.001 & later

“Step Logic” 20

[Jog Frequency]

This parameter sets the frequency the drive will output
when it receives a valid jog command.

Parameter Number

24

Parameter Type

Read and Write

Display Units / Drive Units

0.1 Hertz / Hertz x 100

Factory Default

10.0 Hz

Minimum Value

0.0 Hz

Maximum Value

400.0 Hz

[Preset Freq 1]
[Preset Freq 2]
[Preset Freq 3]
[Preset Freq 4]
[Preset Freq 5]
[Preset Freq 6]
[Preset Freq 7]

These values set the frequencies that the drive will output
when selected. Refer to Speed Select Input table in
Chapter 2.

Parameter Number(s)

27-29 & 73-76

Parameter Type

Read and Write

Display Units / Drive Units

0.1 Hertz / Hertz x 100

Factory Default

0.0 Hz

Minimum Value

0.0 Hz

Maximum Value

400.0 Hz