Installation/Wiring

Specifications for the various inputs and outputs are provided below.

1

Use TB2-5 for shield connection.

2

Refer to Typical Isolation diagram below.

I/O Type

Configuration

Specification

Ref.

Standard

0-10V Input

100k ohm input impedance.

TB2-4

1

0-10V Output

Can drive a 10k ohm load (60 mA short circuit
current limit).

TB2-9

1

0-20 mA Input

200 ohm input impedance.

TB2-4

1

10k Ohm Pot. Input 760k ohm input impedance.

Pot. source = 5V through 2.67k ohms to TB2-1.

TB2-4

1

Option
Board

2

0-10V Input

100k ohm input impedance.

TB2-5

0-10V Output

Can drive 3.3k ohms (3 - parallel 10k ohm loads). TB2-5

0-20 mA Input

100 ohm input impedance.

TB2-5

0-20 mA Output

Can drive 400 ohms (3 - series 0-20 mA inputs). TB2-5

Pulse Input

250 ohms in series with an opto LED.

Pulse high is greater than 8 mA or 3.6V, while
pulse low is less than 0.8V or 0.2 mA.

Absolute maximum continuous input level is 12V
or 50 mA.

TB2-9

Pulse Output

Provides a current limited 4.5V square wave.

This output can drive one PLUS or three PLUS II
pulse inputs.

TB2-5

Thermistor Input

5V across 3.3k ohms in series with the
thermistor.
This arrangement limits the measuring voltage to
less than 2.5V (no self-heating).

TB2-4

!

ATTENTION: Configuring an analog input for 0-20mA
operation and driving it from a voltage source could cause
component damage. Verify proper configuration prior to
applying input signals.

Signal

Conditioning

Signal

Option Board

User

I/O

Power

Typical Isolation

True Galvanic Isolation to 200V AC

(greater than 10 M ohm, less than 50 pf).