Pi status, Pi ref select, Process pi – Rockwell Automation 1336F PLUS II User Manual - Firmware 1.xxx-6.xxx User Manual

Page 136

Advertising
background image

6–54

Programming

Process PI

[PI Status]

This parameter displays the status of the Process PI
regulator.

Parameter Number

214

Parameter Type

Read Only

Factory Default

None

[PI Ref Select]

The source of the PI reference is selected with this param-
eter. The value from the selected reference is the “set
point” for the Process PI regulator.

The drive is capable of responding to a loss of the 4-20
mA signal used as either a PI reference or PI feedback.
Response to loss of 4-20 mA signal is controlled by pro-
gramming and requires the following:

a) [Speed Control] must be set to “Process PI”

and

b) Either [PI Ref Select] or [PI Fdbk Select] must be set to

“4-20 mA.”

If both of the above conditions are met, the signal loss
response is controlled by the setting of [4-20 mA Loss Sel].
If this parameter is set to “Stop/Fault,” loss of input will
cause the drive to stop and issue a Hertz Err Fault. Loss
of input while any other setting of [4-20 mA Loss Sel] is
chosen will cause the drive to activate the alarm bit (bit 6
of [Drive Status] and bit 13 of [Drive Alarm]) and output
programmed [Minimum Freq].

Signal loss protection is offered for the 2-10V input.

Parameter Number

215

Parameter Type

Read/Write

Factory Default

“Preset 1”

Units

Display Drive

“Use Last” 0

“Analog In 0” 1
“Analog In 1” 2
“Analog In 2” 3

“Pulse Ref” 4

Refer to [Pulse In Scale] Value

“MOP” 5

“Adapter 1-6” 6-11

“Preset 1-7” 12-18

“Encoder” 19 Refer to [Encoder PPR] Value

Diagram 1

Time

Enable

PI

Output

Command

Output

Freq.

Disable

0

24

21

27

30

18

15

12

9

6

3

Enable PI output integrates from zero – drive ramps

to regulated frequency.

Disable PI output is forced to zero – drive ramps to

unregulated frequency.

Enable PI output steps to preload and integrates

from there – drive steps to preload and
ramps from there.

Disable PI output is forced to zero - drive ramps to

unregulated frequency.

Enable PI output integrates from preload – drive

ramps from preload.

Disable PI output is held at preload - drive ramps to

unregulated speed (min. preload).

Note:

Drive will step output equal to preload on

Diagram 2

Enable

Disable

0

24

21

27

30

18

15

Preload

12

9

6

3

Diagram 3

Enable

Disable

0

24

21

27

30

18

15

12

9

6

3

Preload

Preload

Preload at Start

Preload at Start

Preload

Feed forward effect for
more dynamic

Better response for
well defined

Bit 7 Bit 6 Bit 5

Bit 4 Bit 3 Bit 2

Bit 1 Bit 0

Enabled
Spares

Advertising