Pi fdbk select, Pi reference, Pi feedback – Rockwell Automation 1336F PLUS II User Manual - Firmware 1.xxx-6.xxx User Manual

Page 137: Pi error, Pi output, Ki process, Process pi

Advertising
background image

Programming

6–55

Process PI

[PI Fdbk Select]

The source of the PI feedback is selected with this param-
eter. It identifies the input point for the process feedback
device.

Parameter Number

216

Parameter Type

Read/Write

Factory Default

“Analog In 1”

Units

Display Drive

“Use Last” 0

“Analog In 0” 1
“Analog In 1” 2
“Analog In 2” 3

“Pulse Ref” 4

Refer to [Pulse In Scale] Value

“MOP” 5

“Adapter 1-6” 6-11

“Preset 1-7” 12-18

“Encoder” 19 Refer to [Encoder PPR] Value

[PI Reference]

This parameter displays the current value of the reference
selected by [PI Ref Select].

Parameter Number

217

Parameter Type

Read Only

Display Units / Drive Units

0.01 Hertz / 32767 = Maximum Freq Forward

Factory Default

None

Minimum Value

–400.00 Hz

Maximum Value

400.00 Hz

[PI Feedback]

This parameter displays the current value of the reference
selected by [PI Fdbk Select].

Parameter Number

218

Parameter Type

Read Only

Display Units / Drive Units

0.01 Hertz / 32767 = Maximum Freq Forward

Factory Default

None

Minimum Value

–400.00 Hz

Maximum Value

400.00 Hz

[PI Error]

The value of the error calculated by the PI loop. This value
is the difference between [PI Reference] & [PI Feedback]
and determines the PI output.

Parameter Number

219

Parameter Type

Read Only

Display Units / Drive Units

0.01 Hertz / 32767 = Maximum Freq Forward

Factory Default

None

Minimum Value

–400.00 Hz

Maximum Value

400.00 Hz

[PI Output]

The current output of the PI loop is displayed with this
parameter. This output is used as the speed command for
process control or the speed adder for process trim.

Parameter Number

220

Parameter Type

Read Only

Display Units / Drive Units

0.01 Hertz / 32767 = Maximum Freq Forward

Factory Default

None

Minimum Value

–400.00 Hz

Maximum Value

400.00 Hz

[KI Process]

This parameter sets the integral gain of the process PI
loop.

Parameter Number

221

Parameter Type

Read/Write

Display Units / Drive Units

NA / NA

Factory Default

128

Minimum Value

0

Maximum Value

1024

Advertising