Start-Up

5–7

5. Set [Maximum Freq] and [Maximum Voltage] parameters to correct values

(typically line voltage/frequency). Set [Base Voltage] and [Base Frequency]
parameters to the motor nameplate values.

A. From the Status Display, press the Enter key (or any key). “Choose Mode”

will be displayed.

B. Press the Increment (or Decrement) key until “Program” is displayed.

C. Press Enter.

D. Press the Increment key until “Setup” is displayed.

E. Press Enter.

F.

Press the Increment or Decrement keys until “Maximum Freq” is displayed.
Press SELect. The first character of line 2 will now flash.

G. Use the Increment/Decrement keys to display the first digit, then press Enter.

Repeat for remaining digits.

H. Repeat the above steps to program the remaining parameters located in

the Motor Control group.

I.

Press the ESCape key (3 times) to return to the Status Display.

Choose Mode

EEProm

Choose Mode

Program

Metering

Setup

Input Mode

3 Wire

Maximum Freq

60

Stopped

+0.00 Hz

Choose Sensorless

Vector or V/Hz

6. Sensorless Vector or V/Hz operation.

Sensorless Vector or Volts/Hertz operation is selectable via [Control Select].
Vector operation is the default. If V/Hz operation is desired, reprogram [Control
Select] using the steps above as a programming guide. Refer to Chapter 6.

Advanced Start-Up Procedure

Press these keys . . .

while following these steps . . .

The HIM Display will show . . .

or

or

or

&